Item Description
600kW / 750kVA Gillette Generators SPVD-6000 standby diesel generator powered by a Volvo Penta TWD1643GE engine and coupled to a Stamford HCI634G alternator. Unit features a Basler DGC-2020 digital controller, brushless excitation system, Class H insulation, and multiple voltage configurations including 480V and 600V three-phase outputs. Available as an open skid package or with a weatherproof sound-attenuated enclosure. Ideal for utility backup, industrial facilities, oilfield operations, data centers, and critical infrastructure applications. EPA Tier II compliant and built to NFPA, UL, NEMA, and ANSI standards.
Gillette SPVD-6000 — 600 kW Standby Diesel Generator Set
Capacities
Fuel Type: Diesel #2-D (ASTM) — confirmed
Fuel Consumption (100% standby): 40.8 gal/hr — confirmed (75% = 29.7 / 50% = 20.0)
Fuel Tank Capacity: VERIFY on unit (sub-base tank is a separate option, not on spec sheet)
Engine Oil (w/ filter): 44.3 qt — confirmed
Radiator Coolant: 25.1 gal — confirmed
Engine Jacket Coolant: 8.7 gal — confirmed
Category Specific (Generator Set)
Standby Power: 600 kW / 750 kVA — confirmed (120°C rise)
Prime Power: NOT rated on this sheet — SPVD is a standby-only unit
Frequency: 60 Hz — confirmed
Phase: 3-Phase — confirmed
Power Factor: 0.8 — confirmed
Voltage / Amps (match the nameplate) — confirmed:
208V — 2084 A · 240V — 1806 A · 480V — 903 A · 220V — 1970 A · 600V — 722 A
Alternator: Stamford HCI634G-311 (208–240V) / HCI534E-311 (480V) / HCI534F-17 (600V) — confirmed
Insulation Class: H (180°C) — confirmed
Controller: Basler DGC-2020 digital genset controller — confirmed
Enclosure: VERIFY — Open set OR Level 2 sound-attenuated aluminum housing
Sound Level: 98 dB(A) open / 83 dB(A) enclosed (critical silencer) — confirmed
Main Breaker: VERIFY on unit (Eaton Power Defense 800/1200/2000/2500A frames were in the PDF)
Chassis
Battery System: 24 VDC, (2) 12V BCI #31, 1000 CCA min, w/ charger — confirmed
Vibration Isolators: Yes — confirmed (standard)
Exterior
Housing: VERIFY (Level 2 = 9-stage wash, zinc phosphate etch, baked powder coat, 18/8 SS hardware — if enclosed)
Silencer: Bergari critical-grade, P/N 500-008828 — confirmed (spec'd for this engine; standard on Level 2)
Powertrain
Engine Speed: 1800 RPM — confirmed
Hours: VERIFY — pull off controller
Engine
Horsepower: 917 BHP standby @ 1800 RPM — confirmed (674 kWm)
Engine Manufacturer: Volvo Penta — confirmed
Engine Model: TWD1643GE — confirmed
Engine Serial Number: VERIFY — pull off unit
Engine Arrangement: Inline-6, 4-cycle, turbo aftercooled — confirmed
Displacement: 16.1 L / 984 cu in — confirmed
Engine Tier: EPA Tier 2 — confirmed
Governor: Electronic, Volvo EMS 2 — confirmed
Engine Overhaul / Hours Since: VERIFY with owner
Shipping Dimensions
Open Set: 152" L × 72" W × 80" H — Net 9,825 lb / Ship 10,225 lb — confirmed
Level 2 Enclosure: 186" L × 72" W × 94" H — Net 12,325 lb / Ship 12,725 lb — confirmed
Terms of Sale
All items are sold in their current condition ("as-is, where-is"), without any warranties, representations, or guarantees, whether express or implied.